TMV servicing across the UK

TMV3 valve servicing

TMV Servicing Specialists services, tests and replaces TMV3 valves in care homes, hospitals, clinics and other settings with vulnerable users across the UK. TMV3 valves meet the NHS D 08 performance specification, and the way they are tested is set out in HTM 04-01 guidance. A partner engineer works through each valve and records results in a form that stands up to inspection.

A thermostatic mixing valve with a temperature test gauge fitted to its outlet

TMV3 valves and the settings that rely on them

TMV3 is the higher-performance approval scheme for thermostatic mixing valves, built on the NHS D 08 specification. A TMV3 valve has to hold its temperature more tightly when supply pressures and temperatures change and shut off faster if the cold supply fails. That is why D 08 and HTM 04-01 Part B expect TMV3 valves at outlets used by people who may not sense or react to hot water quickly: older residents, people with dementia or reduced sensation, patients, and young children in care.

In England, HTM 04-01 is the Department of Health and NHS England guidance for safe water in healthcare premises. Scotland follows SHTM 04-01 and Wales follows WHTM 04-01, and health and social care estates in Northern Ireland adopt the guidance in their own way. Care providers are inspected by the CQC, the Care Inspectorate, Care Inspectorate Wales or RQIA, and each expects providers to manage hot water risks and keep records. TMV3 servicing is where those expectations turn into readings on a sheet.

Choose this service for any building where TMV3 valves are installed or where the people using the outlets need them. For flats and offices without vulnerable users, TMV2 servicing is normally proportionate. If you are unsure whether existing valves carry the right approval, or where valves are missing, a survey should come first.

What a TMV3 service covers

Healthcare and care settings need more than a quick look. Following D 08 Chapter 11, each valve is typically taken through:

  • Valve identificationConfirming the valve is TMV3 approved, recording make, model, location and outlet, and matching it to any register.
  • Temperature at the outletMeasuring the mixed water temperature at the basin, bath, shower or bidet against the maximum set for that outlet type.
  • Supply temperaturesRecording hot and cold supply temperatures, since a low hot supply can mask a faulty valve and points to a Legionella control problem.
  • Fail-safe testIsolating the cold supply and checking the flow stops or reduces to a trickle, then restoring it and checking the temperature returns close to the earlier reading, commonly within 2°C.
  • Strainer and check valve cleaningCleaning inlet strainers and inspecting check valves, which D 08 expects at least annually or as the risk assessment directs.
  • Adjustment and recording driftResetting valves that have drifted and noting how far, because drift determines the next test interval.
  • Remedial listListing any valve that fails, cannot be reached safely or needs a cartridge, repair or replacement.

Plan before the visit

  • Resident and patient routines

    Bathrooms and en-suites are in use day and night. Agree with care staff which rooms can be worked in and when.

  • Infection control

    Share any isolation rooms, outbreak restrictions or PPE requirements so the engineer can plan the order of work.

  • Your current regime

    Provide the last test dates, intervals and readings so new results can be compared and intervals kept on track.

  • Water safety group input

    In hospitals and larger providers, the water safety group or responsible person may want to approve set temperatures and intervals.

TMV3 testing points worth knowing

  • Maximum temperatures by outlet

    Temperatures commonly quoted from D 08 are 38°C for a bidet, 41°C for showers and washbasins, and 44°C for a bath, with up to 46°C for an assisted bath fill where a carer is present. A risk assessment can set lower figures.

  • The testing timetable

    After commissioning, in-service tests are expected at about 6 to 8 weeks and again at about 12 to 15 weeks. After that, the interval depends on drift: around 24 to 28 weeks where the valve holds within about 1°C, and shorter where it moves more.

  • Hand washing still needs warm water

    Setting a washbasin far below 41°C can discourage effective hand washing in clinical areas, so set points balance scald risk against hygiene.

  • TMVs and Legionella meet here

    Hot water reaching TMVs should be at least 55°C in healthcare. Valves should sit close to their outlets to keep mixed-water runs short, and little-used outlets need regular flushing.

Arranging TMV3 work

  1. 1

    Send an enquiry

    Describe the setting, the number of valves or rooms, and the date of the last tests if known.

  2. 2

    Matched to a partner engineer

    Alex selects a partner engineer who covers your area and works in occupied care or healthcare buildings.

  3. 3

    Agree scope and price

    The price depends on valve numbers, access and whether repairs are expected; it is confirmed before work starts.

  4. 4

    Room-by-room testing

    The engineer works around the routine of the building, servicing and testing each TMV3 valve in turn.

  5. 5

    Records for each valve

    A visit usually leaves you with per-valve readings, fail-safe results, logbook entries and a list of further work.

TMV3 valve questions

See all questions

Do care homes have to use TMV3 valves?

Guidance for health and social care expects outlets used by vulnerable people to be protected by valves meeting the D 08 specification, which is what TMV3 approval shows. Regulators expect providers to manage hot water risk in line with that guidance.

How often should TMV3 valves be tested?

D 08 sets in-service tests after commissioning, then an interval based on how much each valve drifts, roughly 24 to 28 weeks for stable valves. Your risk assessment sets the final figure.

What happens if a valve fails the fail-safe test?

It should be taken out of use or the outlet restricted until it is repaired or replaced, and the failure recorded.

Can a TMV2 valve be used in a care home?

Not where vulnerable people use the outlet. A valve with TMV3 approval, or dual TMV2 and TMV3 approval, is normally expected.

Can work happen while residents are in?

Yes, with planning. Each valve is isolated for a short time, so rooms are worked through one at a time with staff.

What records will we get?

You should expect readings before and after, fail-safe outcomes, a record per valve and recommendations, in a form that suits an inspection file.